We develop advanced sensors for:

Industrial refrigeration
01
Commercial Refrigeration
02
Heat pumps
03

Liquid Level Sensor - ATEX

Technical data: HBLT-W-Wire 

HBLT-W-Wire is a capacitive sensor for level measurement in industrial systems.The sensor has an output signal of 4-20 mA, which is proportional with 0 and 100%.Its output signal is 4 mA for an empty tank and 20 mA for a full tank.HBLT-wire can be adjusted in length to the current application.The sensor element consists of a 2mm steel wire as well as a Teflon tube. Both parts are provided with a length of 4 m and can be shortened with diagonal cutters or other pliers. HBLT-wire can be used in connection with the HBLT-C1 controller for controlling pumps.

HBLT-W-Wire - Counterweight with adjustable center position spring

Under turbulent conditions, the counterweight for the HBLT-W-Wire can be supplied as a spare part with an adjustable center position spring. The center position spring is delivered with cutting marks so it can be adapted and cut to the dimension of the stand pipe.                                                        HBLT WIRE Counterweight 2217 fritlagt hvid baggrund Web

The sensor is designed in stainless steel and can be used in corrosive environments. The sensor must be supplied with 24 V DC through an Ex-barrier, which must be an approved and certifided galvanically isolated interface barrier placed outside the hazardous area. The sensor is a 2-wire design with analog output with 4 mA (empti tank) and 20 mA (full tank). The analog output shall be connected to the Ex-barrier. The Ex-barrier is not sccope of supply.  

The sensor can be set-up for liquid type in the HB-Tool which can be downloaded from our web-page. See HB-Tool. Diagnostic is as well a possibility with the tool. The programming must be carried out in an non hazardous area. 

The sensor range include sensors for zone 0 and 1 according to ATEX/IECEx. The sensors can be used in device category 1G and temperature class T1...T6.   

A 5 m cable with M12 plug type IEC61076-2-101 is included. 

 

Product features

  • Temperature range: -40...+70°C.
  • Max pressure: 150 bar
  • ATEX / IECEx: Ex ia  IIC T1…T6 Ga (Ta = -40°C to +70°C) 
  • Excellent liquid and gas compatibility 
  • Cost effective alternative to ultrasonic & radar sensor technologies 
  • Works with reflective liquids 
  • Will not fail due to vapor 
  • No galvanic corrosion 
  • Split design which makes it easy to install and make diagnostic. 

Applications

 Applications

  • Process plants
  • Storage tanks

Intrinsically Safe design:

Intrinsically Safe (IS) sensors are designed and wired to work on such a low current and voltage that it cannot possibly ignite flammable material. By limiting the energy available within the defined hazardous area, electrical equipment can operate safely even amid hazardous mixtures of gasses.

The HBLC sensor is designed for many kinds of liquidsbased on the dielectric constant. The liquid type is selected in the HB-Tool. 

The measuring principle and the influence of the dielectric constant:

Capacitors are designed with minimum two conductors, where one of them is electric isolated. The dielectric constant are key for operation of capacitors, the capacity size is measured in pF.

Dielectric constant (Relative permittivity) is a unique value on a scale of 1 to 100. The value can be seen as a media’s DNA, because it`s unique and related to the molecular structure and polarization.

The Dielectric Constant is always greater than or equal to 1. The larger the dielectric constant, the more charge can be stored (like a battery).

The dielectric constant changes with temperature and pressure, the sensor comes with automatic temperature compensation calibrated/adapted to the measured media.

Type of switches:

Sensor type                Liquid type                                                                                                   Dielectric constant

HBLC-CO2                CO2(R744), Butane (R600), Isobutane (R600A), Propane (R290)             1.5-2.0
HBLC-OIL                  PAO oil, Mineral oil, POE oil, PAG oil                                                          2.0-4.0
HBLC-HFC                R507, R410a, R407c, R404a, R22, R32, R134a, R1234yf, R1234ze         4.0-10.0
HBLT-A2                    NH3, Water, R717, R718, Alchohol                                                             10.0-80.0

Specifications

Connection diagram

Diagram sensor

The sensor can be programmed to either emit a linear signal, which is identical to the tank level, or to regulate a valve for the purpose of obtaining the same level in the tank (float valve).

Drawing

HBLT Wire ex

Power supply
Voltage12-28 V DC two wire
Max. current consumption Max 20 mA
Plug connectionsM12, 5 pins - DIN 0627
Output
Signal output 4...20 mA (AO)
Mechanical specifications
Material liquid partsAISI 304 / PTFE
Material electronic partsNylon 6 (PA)
Environmental conditions
Max pressure150 bar
Protection degreeIP65
VibrationsIEC 68-2-6 (4g)
EMCEN 61000
HBP_PRODUCT_TAB_SPECS_STR_ATEX
IECEx classificationEx ia IIC T1…T6 Ga
Device category1G for Zone 0 & 1
Type of protectionia
Gas resp. gas groupIIC
Temperature classT1….T6
Ambient temperature-40...+50°C/+70°C
When used in Ex-area the installation has to be carried out according to standards in force for the country in question.
The Equipment must be installed via an approved and certified galvanically interface barrier placed outside the hazardous area.

Ordering code

600-4000 mm 3/4" NPTZone 1HBLT-W-Wire-2-Z1 600-4000 mm 3/4" BSPPZone 1HBLT-W-Wire-6 -Z1 600-6000 mm 3/4" NPTZone 1HBLT-W-Wire-6-2-Z1 600-6000 mm 3/4" BSPPZone 1HBLT-W-Wire-6-6 -Z1 600-4000 mm 3/4" NPTZone 0HBLT-W-Wire-2-Z0 600-4000 mm 3/4" BSPPZone 0HBLT-W-Wire-6 -Z0 600-6000 mm 3/4" NPTZone 0HBLT-W-Wire-6-2-Z0 600-6000 mm 3/4" BSPPZone 0HBLT-W-Wire-6-6 -Z0 Electronic part for HBLT-WireZone 1HBLT-Wire-EL-Z1 Electronic part for HBLT-WireZone 0HBLT-Wire-EL-Z0 Accessories 1"BSPP -> 3/4"BSPP adapter with alu gasket HBS/ADAP/8/6 Counterweight for HBLT-Wire HBLT-W-COUNTERWEIGHT Spareparts Weight for HBLT-Wire HBLT-WIRE-PLUMB

Downloads