We develop advanced sensors for:

Industrial refrigeration
01
Commercial Refrigeration
02
Heat pumps
03

CO2 Gas Leakage - Detection

Product Series: HBGS

HBGS fulfils the requirements for gas leakage measurement in accordance with F-GAS regulation EU/517/2014. HBGS detects CO₂ (R744) in a range of 0…10000 ppm. It is an independent unit that must be supplied with 24 V DC. It has 3 built-in digital alarm output and 1 analog 4… 20 mA output. The sensor can be set up using a PC with the HB Configuration Tool.

The CO₂ sensor version has a lifetime of more than 5 years. Both sensor elements can easily be replaced and does not require a new calibration. On the front, you can find 4 integrated LEDs for display of the supply (green) as well as 3 alarm levels (red, orange, and yellow). Similarly, there is a reset button in case an alarm is triggered. The sensor is factory calibrated. Verification during the lifetime can be done with high gas concentrations. The sensor is optimized for use in areas where cleaning solvents are used. Built-in heating element ensures low ambient temperatures down to -30 ° C. The sensor comes with a calibration certificate as well as with preconfigured alarm limits.

Product features

  Integrated LED's for display of the supply (green) as well as 3 alarm levels (red, orange and yellow).
  The sensor is factory calibrated and does not require additional calibration at startup. The sensor comes with a calibration certificate as well as with configured alarm limits.
Supply voltage: 24 V DC - Power consumption max 3 watt
Reset button in case an alarm is trigged

Alarm limits: o....1000 ppm (can be configured with HB-tool).

Standard factory settings:
Alarm A: 800 ppm NO/NC (Main alarm acc. to EN378)
Alarm B: 500 ppm NO/NC (Pre-alarm acc. to EN378)
Alarm C: 200 ppm NO/NC (Pre-alarm acc. to EN378)

The HBGS can also be ordered with customized default settings based on specific customer needs.

Specifications

Electrical installation

HBGS web 

Drawing

 HBGS NH3 KOMP R3 1 Small

 

 
Power supply
Power supply24 V DC - Power consumption max 3 watt
ConnectionScrew terminals
Cable glands2 x PG7
AlarmCan be configured with HB-tool and an USB cable and an adapter
Alarm limits0 to 10000 ppm for CO2
Measurement accuracy NH3Repeatability +/-10%
Analog output4...20 mA
Max load500 ohm
Alarm output, relay3 x SPDT, 0,5A
Environmental conditions
Ambient temperature-30...+50°C
Protection degreeIP20, box IP65
Mechanical specifications
Cabinet size82x59x126 
MaterialPlastic
MountingOn walls with screws
Approvals
EMC EmissionEN 61000-6-4
EMC EmissionEN 61000-6-2
Accessories
Alarm device - part number Sounder Beacon
Alarm  can be configured with HB-tool
Alarm limits0 to 10000 ppm
Alarm A8000 ppm NO/NC (Main alarm acc. to EN378)
Alarm B5000 ppm NO/NC (Pre-alarm acc. to EN 378)
Alarm C2000 ppm NO/NC (Pre-alarm acc. to EN 378)

Ordering code

0...10000 ppmCO2HBGS-CO2 AccessoriesGasOrdering code Part no. Service kit for verificationCO2 (R744)HBGS-ServiceKit Part no. Sounder/flash lightCO2 (R744)Sounder Beacon

Downloads